SRP981
SRP981 Pneumatic Positioner
Description
The SRP981 Positioner is for operation of pneumatic valve actuators with pneumatic control signals. It is used to reduce the adverse effects of valve friction, for higher thrust and shorter positioning time.
FEATURES
- Independent adjustment of stroke range and zero
- Adjustable amplification and damping
- Split range up to 4-fold possible
- Supply pressure up to 6 bar (90 psig)
- Low vibration effect in all directions
- Mounting according to IEC 534, part 6 (NAMUR)
- Rotation adapter for angles up to 120 °
- Ambient temperature –40 to 80 °C (–40 to 176 °F)
- Travel 8 to 100 mm (0.3 to 4 in)
- Angular range 30 ° to 120 °
- Modular system of additional equipment
- Electrical limit switches
- Electrical position transmitter
- Booster
- Connection manifold
- Protection class IP54 (IP 65 on request)
- Certificate No. 90/20226(E2) Lloyd’s Register of Shipping for use on vessels
- Explosion Protection
- pneumatic basic device: ATEX II 2 G c IIC T6 constructive design
- electrical additional built-in equipment: ATEX II 2 G Ex ib/ia IIB/IIC T4/T6 CU TR explosion protection
SPECIAL VERSION OF SRP981
SRP981 in Stainless Steel housing
Casing | Stainless Steel 1.4404 / 316L, 1.25 mm thick |
Ingress Protection | IP65; IP66 under working conditions (supplied by air supply) |
Impact Resistance | > 7 Joule acc. to EN 50014 |
Seals | VMQ (Silicone) |
For dimensional drawings see further down this page
Version for mounting to linear actuators, single acting can be ordered under special version ECEP EP 0301, together with Mounting kit EBZG. Other versions for double acting or mounting to rotary actuators on request.
TECHNICAL DATA
Input
Signal range | 0.2 to 1 bar (3 to 15 psig) or split range down to ∆w 0.2 bar (3 psi) |
Stroke range | 8 to 100 mm (0.3 to 4 in) |
Angular range linear | 30 ° to 120 ° |
equal percentage | 90 °; from 70 ° linear |
Output
Output to actuator | 0 to 100% supply air pressure |
Supply
Supply air pressure | 1.4 to 6 bar (20 to 90 psig) |
Air supply - Solid particle size and density - Oil rate - Pressure dew point 10 K under ambient temperature |
according to ISO 8573-1 |
For air supply, we recommend the FRS02 filter regulator. |
Ambient conditions
Ambient temperature | –40 to 80 °C (–40 to 176 °F) |
Relative humidity | up to 100% |
Operating condiutions
Operating conditions as per IEC 654-1: The device can be operated at a class D2 location
Transport and Storage
Temperature | –50 to 80 °C (–58 to 176 °F) |
Protection Class | IP 54 (IP 65 on request) |
Response characteristic
Amplification | adjustable |
Sensitivity | < 0.1 % F.S. |
Non-linearity (terminal based adjustment) | < 0.1 % F.S. |
Hysteresis | < 0.3 % F.S. |
Supply air dependency | < 0.2 % / 0.1 bar (1.5 psi) |
Temperature effect | < 0.3 % / 10 K |
Air consumption
supply air pressure | air consumption |
Single acting | |
1.4 bar (20 psig) | 200 ln /h ( 7.1 scfh) |
3.0 bar (45 psig) | 400 ln /h (12.4 scfh) |
6.0 bar (90 psig) | 600 ln /h (21.2 scfh) |
Double acting | |
1.4 bar (20 psig) | 350 ln /h (10.6 scfh) |
3.0 bar (45 psig) | 550 ln /h (17.7 scfh) |
6.0 bar (90 psig) | 750 ln /h (33.5 scfh) |
Air output
Load effect | –3 % for delivery flow 2 350 ln /h (83 scfh) |
+3 % for exhausted flow 1 900 ln /h (67 scfh) |
Capacity at max. deviation
Supply air |
1.4 (20) | 2 (30) | 4 (60) | 6 (90) |
without booster ln/h (scfh) | 2700 (95) | 3500 (124) | 5500 (194) | 7500 (265) |
with booster code VKXG -FN ,-GN ln/h (scfh) | 18000 (636) | 24000 (847) | 40000 (1412) | 55000 (1942) |
with booster code VKXG -HN ln/h (scfh) | 36000 (1271) | 48000 (1695) | 80000 (2825) | 110000 (3884) |
Data measured according to VDI/VDE 2177
Material
Base Plate | Aluminum (Alloy No. 230) finished with DD-varnish blue |
Cover | impact resistant polyester blue |
All moving parts of feedback system | 1.4305 / 1.4571 |
Mounting bracket | 1.4301 |
Weight
Single acting | |
without gauges | approx. 0.7 kg (1.5 lbs) |
with gauges | approx. 0.8 kg (1.8 lbs) |
Double acting | approx. 0.9 kg (2.0 lbs) |
Attachment kit | |
for diaphragm actuators | approx. 0.3 kg (0.6 lbs) |
for rotary actuators | approx. 0.5 kg (1.1 lbs) |
Connection
Pneumatic | Female threads G 1/8 acc. to ISO 228 |
Mounting
Type of mounting | for attaching to diaphragm actuators acc. IEC 534-6 (NAMUR |
for attaching to rotary actuators | |
Mounting orientation | any |
Gauges
Indicating range | |
Input | 0 to 1.6 bar (0 to 23 psig) |
Output | 0 to 10 bar (0 to 150 psig) |
Error limit | class 1.6 |
Accessories
Connection Manifold With Gauges Code J, M
Indicating range | 0 to 10 bar (0 to 150 psig) |
Error limit | class 1.6 |
Pneumatic connections | Female threads Q 1/4-18 NPT acc. to DIN 45 141 |
Connection Manifold with Gauges Code K, L, N
Indicating range | |
Supply, output | 0 to 10 bar (0 to 150 psig) |
Input | 0 to 1.6 bar (0 to 23 psig) |
Error limit | class 1.6 |
Pneumatic connections | Female threads Q 1/4-18 NPT acc. to DIN 45 141 |
Additional Equipment
(built-in into basic device)
Inductive Limit Switch
Code T, U Two-wire System
Input | Stroke / angle from actuator via positioner feedback lever |
Output | 2 inductive proximity sensors acc. to DIN 19234 or NAMUR for connection to a switching amplifier with an intrinsically safe control circuit |
Current consumption | Vane clear > 3 mA Vane interposed < 1mA |
For control circuit with the following electrical values
Supply voltage | DC 8 V, Ri approx. 1 kOhm |
Residual ripple | < 5 % |
Permissible line resistance | < 100 Ohm |
Response characteristic
Gain | Continuously adjustable from 1:1 to approx. 7:1 |
Switching differential | < 1 % |
Switching point repeatability | < 0.2 % |
Inductive Limit Switch
Code R Three-wire system
Input | Stroke / angle from actuator via positioner feedback lever |
Output | 2 inductive proximity sensors, three-wire system, LEDindication, contact, pnp |
Supply voltage Us | DC 10 to 30 V |
Residual ripple | ±10 %, Us = 30 V |
Switching frequency | 2 kHz |
Constant current | 100 mA |
Response characteristics
Gain | Continuously adjustable from 1:1 to approx. 7:1 |
Switching differential | < 1 % |
Switching point repeatability | < 0.2 % |
Parts set for later installation
Code R | EW 419 510 291 |
Limit Switch Assembly with Micro switches
Code V
Input | Stroke / angle from actuator via positioner feedback lever |
Output | 2 micro-switches |
Connected load
Alternating current | |
Switching capacity | max. 250 VA |
Switching voltage | max. 50 V |
Switching current with ohmic resistance | max. 5 A |
inductive resistance | max. 2 A |
Bulb, metal filament | max. 0.5 A |
Direct Current
Switching voltage, max | Ohamic load | Inductive load |
30 V 50 V |
5 A |
3 A 1 A |
Response Characteristic
Gain | Continuously adjustable from 1:1 to approx. 7:1 |
Switching differential | < 2.5 % |
Switching point repearability | < 0.2% |
Parts set for later installation
Code V | EW 420 421 017 |
Electrical Position Transmitter
Code W
Input | Stroke / angle from actuator via positioner feedback lever |
Sensor | resistive precision conductive plastic element |
Stroke range | 15 to 80 mm (0.6 to3.15 in) < 15 mm (0.6 in) on request |
Angular range | 60 to 120 ° |
Output | Two-wire system |
Signal range | 4-20 mA |
Permitted load | RB max = (US–12 V)/0.02 A (US = supply voltage) |
Power supply
Supply voltage | DC 12 to 36 V |
Permitted ripple | < 10 % p.p. |
Supply voltage dependency | < 0.2 % |
Response characteristic
Non-linearity with terminal based setting | < 1.0 % F.S. |
Hysteresis | < 0.5 % F.S. |
External resistance dependency | < 0.2 % / ∆ RB max |
Temperature effect | < 0.3 % / 10 K |
Explosion protection
Type of protection | II 2 G Ex ib/ia IIB/IIC T4/T6 |
Certificate of conformity | PTB 02 ATEX 2153 |
For operation in certified intrinsically safe circuits with the following maximum values:
Umax | T4: 30 V | T6: 22 V |
Imax | T4: 130 mA | T6: 66 mA |
Pmax | T4: 0,9 W | T6: 0.5 W |
Internal inductance | 9 µH | |
Internal capacitance | to earth 10 nF or 6 nF differentia |
Ambient temperature
Temperature class | T6 | –40 to 40 °C (–40 to 104 °F) |
T5 | –40 to 55 °C (–40 to 131 °F) | |
T4 | –40 to 80 °C (–40 to 176 °F) |
Parts set for later installation
Code W | EW 420 661 115 |
Common Data
Ambient conditions
Ambient Temperature | –25 to 80 °C (–13 to 176 °F) –40 to 80 °C (–40 to 176 °F) |
Relative Humidity | up to %100 |
Operating conditions as per IEC 654-1 | The device can be operated at a class D2 location |
Transport and storage
Temperature | –40 to 80 °C (–40 to 176 °F) |
Protection class | IP 54 (IP 65 on request) |
Electrical connection
Line entry | 1 or 2 cable glands M20x1.5 (others with Adapter AD-...) |
Cable Diameter | 6 to 12 mm (0.24 to 0.47 in) |
Screw terminals | Screw terminals for wires up to 2.5 mm2 (AWG 14) |
Materials
Base plate | Galvanized steel |
Control vane | Aluminium |
Setting mechanism | Fiber glass-reinforced polyamide |
Electromagnetic compatibility EMC
Operating conditions | industrial environment |
Immunity according to
NAMUR recommendation NE21 | fulfilled |
EN 61 326 | fulfilled |
EN 61 000-6-2 | fulfilled |
Emission according to
EN 55 011, Group 1, Class A | fulfilled |
EN 61 000-6-2 | fulfilled |
CE marking
Electromagnetic compatibility | 2004/108/EG |
Low voltage regulations | w/o Ex: 73/23/EWG fulfilled (with Ex: not applicable) |
Safety
as per DIN EN 61010-1 (DIN IEC 61010-1) (VDE 0411 part 1) | safety class III |
overvoltage category | 1 |
internal fuses | none |
external fuses | Limitation of power supplies for fire protection has to be observed due to EN 61010-1 9.3. ff. |
MODEL CODES SRP981
MODEL CODES Accessories
ATTACHMENT KIT FOR DIAPHRAGM ACTUATORS
ATTACHMENT KIT FOR ROTARY ACTUATORS
DIMENSIONS Additional equipment
DIMENSIONS Additional equipment
DIMENSIONS SRP981 Special version in Stainless Steel housing
DIMENSIONS, CONNECTIONS
If you require further information on this product or would like a quotation, please contact dp-flow on:
email: sales@dp-flow.co.uk
sales +44(0)1608 544222