Accutech SI10 Wireless Switch Input
Seamless Wireless Monitoring for Switch Inputs
Overview:
Accutech SI10 Wireless Switch Input Field Unit
The Accutech™ SI10 wireless switch input field unit monitors contact switches without field wiring. It supports two switch contacts with debounce filtering or as a counter for state changes up to 5 Hz. Optional switch outputs can control external power sources up to 1 A at 30 Vdc. Data is reported wirelessly to a centralized Accutech base radio up to 3000 ft. (1000 m).
Key Facts and Features:
- Sensor Type: Switch-Input with optional Switch Outputs
- Frequency Range: 900 MHz and 2.4 GHz license-free bands
- Inputs: Two contact-closure, can operate in counter mode (up to 5 Hz)
- Outputs: Optional switch outputs, max 1 A at 30 Vdc
- Accuracy: ± 0.1% of full-scale reading
- Operating Temp: -40...+85 °C (-40...+185 °F)
- Humidity: 0...95%, non-condensing
- Materials: 316L stainless steel, epoxy-coated aluminum
- Battery Life: Up to 10 years
- User-Friendly: LCD display with membrane-switch buttons
- Self-Diagnostics: Continuous monitoring with error alerts
- Local Configuration Interface: Configure sampling and RF parameters using membrane-switch buttons
- Remote Configuration: Via Accutech Manager software
- Network Capacity: Supports up to 100 units per base radio and 256 base radios per network
- Low Battery Notification: One month advance alert
Benefits:
- Wireless Flexibility: Reliable communication up to 3000 ft (1000 m)
- Battery Efficiency: Long battery life with configurable sampling rates
- Scalability: Supports large networks with many field units
- Versatile Applications: Ideal for monitoring switch states wirelessly
Applications:
- Monitoring contact switches
- State change counting
- Remote switch control
Technical Specifications:
Operating Temp:
-
- Electronics: -40...+85 °C (-40...+185 °F)
- Display: -40...-20 °C (-40...-4 °F)
- Humidity: 0...95%, non-condensing
- Materials: 316L stainless steel, epoxy-coated aluminum
- Power: 1 D-cell Lithium Thionyl battery
Communication:
-
- 900 MHz: 902...928 MHz, 19.2 kbps and 76.8 kbps
- 2.4 GHz: 2400...2483.5 MHz, 50/100 kbps
- Environmental Testing: IEC 60068-2-6 (vibration), IEC 60068-2-27 (shock)
- EMC: IEC 61000-6-2, IEC 6100-6-4
- Output Resolution: 24-bit analog-to-digital conversion
Download PDF: Accutech SI10 Datasheet
Supplied by DP-Flow
If you require further information on this product or would like a quotation, please contact dp-flow on:
email: sales@dp-flow.co.uk